At +2°C and +7°C the heat delivered from the heat pump exceeds the required heat from the house and is therefore operated in part load. COP for part load operation is interpolated by using the equation for staged capacity units at page 26 in the standard. At +2°C the interpolation is made between full load operation and operation at 47% part load, at +7°C the interpolation is made between part load operation at 57% and 44% of the heat pump capacity.  
The heat pump is not tested at +12°C. Full load operation at +12°C is extrapolated from test data at +7°C and +2°C. 50% part load is extrapolated from 50% part load operation at +7°C and +2°C. COP for the required effect is extrapolated by using this data. Each extrapolated COP value is corrected with a degradation factor of 0.975.  
Default values are used for the degradation factor (Cd=0.1), turndown ratio heating (=25%), thermostat off mode (50W), crank